ANDREW PHILLIPS EXPLAINS HOW TO ENSURE THE CORRECT SPECIFICATION OF RADIATORS.

Despite action by regulators and industry groups such as The Manufacturers’ Association of Radiators and Convectors (MARC), the issue of misleading Delta T figures on radiators still persists.

The effectiveness of any heating system depends heavily on matching radiators to the heating demands of the space. Accurate selection is only possible when radiator outputs are based on the appropriate Delta T value, ensuring the specified heat output reflects real operating conditions.

Undersized or oversized radiators can cause uncomfortable indoor temperatures, increased energy consumption and reduced efficiency. In many cases, specification errors can be traced back to the Delta T values used to calculate radiator outputs.

Delta T is the difference between the average water temperature in the heating system and the target ambient room temperature. The greater the Delta T, the hotter the radiator surface will be and the more heat it will produce. If this figure is incorrect when specifying a radiator, the calculation used to size the radiator will also be incorrect.

Where the issues lie

The Construction Products Regulation 2011 places a legal obligation on manufacturers, including importers, distributors and resellers, to provide verified information about a product’s thermal performance.

To comply, every hydronic radiator, including heated towel rails, must be tested independently in accordance with BS EN 442 standards by an accredited independent laboratory. The test results must then be documented in a Declaration of Performance (DoP), which specifies the radiator’s heat output in Watts at both Delta T50 and Delta T30.

Delta T50 is the recognised standard rating for radiator performance, while Delta T30 is used to assess suitability for lower-temperature systems.

However, some manufacturers and resellers state outputs in their materials, documents or websites that are based on Delta T60 or greater, which assumes higher system water temperatures.

As a result, heating professionals can receive an exaggerated impression of the radiator’s output. If this is used as the basis for heating calculations, the radiators may be undersized, leading to higher energy consumption and increased bills for customers.

This may also affect customer confidence in modern heating systems, including heat pumps, where accurate heat outputs are even more critical because of their lower operating temperatures.

What you need to know

To avoid system performance issues, installers should only use products sourced from manufacturers that can provide independently verified product testing to support their performance data.

Under both UK and EU law, manufacturers must supply a Declaration of Performance for each radiator if requested, in either paper or electronic form. This should also contain details of the organisation that carried out the tests, including verification from notified bodies.

Suppliers should also look for membership of MARC in the DoP, as this can be a good indication of reliability and credibility.

MARC is working with the Office for Product Safety and Standards, the body responsible for enforcing the Construction Products Regulations, to stop manufacturers from providing misleading performance values.

MARC has also been raising awareness of the issue to ensure specifiers and customers understand the problem and can make well-informed decisions.

As a member of MARC, The Radiator Company is committed to supporting the organisation’s efforts to increase awareness of this important issue.